Support

Interface Integra-TR to AB SLC 5/0X

SB ABSLC5/0X

This support bulletin describes the interface information required to connect an Allen Bradley SLC5 to a Dataradio Integra-TR

Insert Figure 1. Cable Interface

Insert Figure 2. Cable Interface ABSLC5/0X PLC Channel Configuration

Channel 0 - System

  • Driver: DF1 Half-duplex Master
  • Baud: 9600 bps
  • Parity: None
  • Stop Bits: 1
  • Node Address: 1 (dependent on application)

Protocol Control

  • Control Line: Half Duplex/wo Continuous Carrier
  • Error detection: CRC
  • Polling Mode: Don’t allow Remotes to initiate
  • Duplicate Packet Detect: Disabled
  • Reply Msg. Timeout (x 20 ms): 1(dependent on application)
  • Use NO HANDSHAKE MODE for both ends of link. Values below only for Handshake control.
  • ACK Timeout (x 20 ms): NA
  • RTS Off Delay (x 20 ms): NA
  • RTS Send Delay (x 20 ms): NA
  • Message Retries: 3
  • Pre Transmit Delay: 0

Insert Figure 3. Integra-TR Field Programming Software Setup Modem Tab

  • Modem Type: Fixed as per the attached unit
  • Short ID: User assigned
  • Serial No.: Factory assigned
  • Comment: User supplied comment
  • Compatibility: Integra-TR
  • Data Delivery: All or Selective
  • Sleep Mode: Disabled (usually)
  • Network Speed: Equal to or greater than data speed
  • Station ID_CWID: Special Use-refer to manual
  • TX Online Diags: Checked (On)
  • CWID Interval: Refer to manual
  • Extended Preamble: Default is 5
  • Suspend Period: Power savings mode- refer to manual
  • Activity Timeout: Power saving mode- refer to manual

Insert Figure 4. Integra-TR Field Programming Software Setup COM/Analog Tab

  • TX Control: Check DOX
  • DCD Control: Switched
  • DTE Baud Rate: 9600 (or as required)
  • DTE Data Format: 8 bits, No parity, 1 Stop (required set-up by DF-1)
  • Data Forward Timer: Normal
  • Break: Ignore break
  • Deferred Rx-Data Delivery: 0-Typically not needed for DF-1
  • Analog 1: Input is default- Tx Controlled Fan in base station or fan equipped TX module
  • Analog 2: Input is default

Insert Figure 5. Integra-TR Field Programming Software Setup Radio Tab

  • Parameters:
  • Radio: Displays unit model
  • Range: Displays unit range
  • Channel: Half (12.5 kHz)
  • Tune Range: Low Rx
  • Transceiver Type: Transceiver - always choose this setting
  • Carrier Sense & Tx Timeout: User programmable - always begin with factory default.
  • Disable Tx w/ Carrier Present: Disabled
  • Radio Frequencies: Displays user frequencies
  • Tx Power: 255 is max 255= 5 watts (not linear, i.e., 128 is not exactly 2.5 W)

Factory defaults are recommended for beginning settings. Refer to the Integra-TR Technical Manual (001-4008-101).